D.A.F. Automazione: custom-made solutions design, production and sale of automation technology, chemicals dosing, electronic flow-measuring, PLC and industrial automations.

D.A.F. Automazione: custom-made solutions design, production and sale of automation technology

Flow Meter SSD01-FM]

Counter Version

Flow Meter SSD01–FM Flow Meter SSD01–FM It is a programmable device designed for instant flow-rate measuring, particularly useful in control systems. It can correct pulses transmitted from flow-rate transducers, display amounts of dosed product and provide an outbound signal, either in voltage or in current, which is directly proportional to the flow rate.

Functioning

Once data is entered, an output current of 4 mA (or 0 V) is generated by the system. When the preset maximum flow rate is reached, the full-range output current of 20 mA (or 10 V) is generated.
The amount of fluid flowing through the hydraulic system is displayed in liters.

Features

  • 24 V AC (200 mA) power supply
  • 9-digit LCD display
  • Data saving with rechargeable battery
  • Pulse correction (percent): 0 ÷ 99.9%
  • Flow-rate measuring with 4 - 20 mA (0 - 20 mA) output current
  • Flow-rate measuring with 0 - 10 V output current (alternative to current signal)
  • Counting error index: 0.1%
  • Linearity of the flow-rate/current curve: 1%
  • Linearity of the flow-rate/voltage curve: 1%
  • Max input frequency: 30 cps (1 kcps on demand)
  • Voltage-free contact (or PNP static contact on demand)
  • Max load RL = 200 Ohm
  • Watertight box IP55, dimensions in mm 120 x 80 x 50
  • Operation temperature max 50 °C.

Function/mode settings

  • MODE 1: press the PROGRAM button until the ”Programming” LED lights up. Enter the desired pulses-per-liter ratio (percent) by pressing the PRESET button.
    E.g.: For a flow meter set at 19.2 pulses per liter, the coefficient K is found as follows: K = 1/19.2x100 = 5.208%. This figure is to be rounded up to the next decimal position, i.e. 5.21% and entered by pressing PRESET until the number 521 is displayed. Press PROGRAM to confirm (the LED goes off).
  • MODE 2: press the PROGRAM button until the ”Programming” LED blinks. Enter the maximum flow rate as required by pressing PRESET until the corresponding figure is displayed (e.g.: for 100 liters per minute, ”100” must be displayed). To confirm, press and hold down the PROGRAM button until the LED turns off. The system is now ready to operate.

Counter and Prescaler Version

A low-cost, 9-digit counter which can be employed in several applications as flow-meter interface or as a piece-counter. It comes with a one-year-lifetime battery.

Features

  • 9-digit liquid-crystal display
  • 0-999999999 counter
  • Input: relay, microswitch, reed relay
  • On demand: NPN input
  • Inbound pulse frequency: 20 Hz (on demand: 150 Hz with NPN open-collector transistor). Inbound pulse correction: 0.1% ÷ 99.9% with 0,5% error index
  • Power supply: two 1.5V batteries
  • Operation temperature max 50°C
  • IP56 watertight box
  • Dimensions in mm: 120 x 80 x 50.

Settings

Press both the PROGRAM and PRESET buttons until the LED lights up. Enter the correction coefficient by pressing PRESET as the displayed figure increases (e.g. for a 25.6% coefficient, 256 must be displayed). Press and hold down PROGRAM until the LED goes off. System is now ready to operate.

Webattuale: creazione ed ideazione di siti web, da usare, capire e sfruttare con semplicita’ e rapidita’ nel rispetto dei navigatori (x)html - css - webmaster - top of page - P.IVA IT02207040128